Electrical Q&A Part-2
1) Why
We use of Stones/Gravel in electrical Switch Yard
§ Reducing Step and Touch potentials during Short
Circuit Faults
§ Eliminates the growth of weeds and small plants
in the yard
§ Improves yard working condition
§ Protects from fire which cause due to oil
spillage from transformer and also protects from wild habitat.
2) What
is service factor?
§ Service factor is the load that may be applied
to a motor without exceeding allowed ratings.
§ For example, if a 10-hp motor has a 1.25 service
factor, it will successfully deliver 12.5 hp (10 x 1.25) without exceeding
specified temperature rise. Note that when being driven above its rated load in
this manner, the motor must be supplied with rated voltage and frequency.
§ However a 10-hp motor with a 1.25 service factor
is not a 12.5-hp motor. If the 10-hp motor is operated continuously at 12.5 hp,
its insulation life could be decreased by as much as two-thirds of normal. If
you need a 12.5-hp motor, buy one; service factor should only be used for
short-term overload conditions
3) Why transmission line 11KV OR 33KV,
66KV not in 10KV 20KV?
§ The miss concept is Line voltage is in multiple
of 11 due to Form Factor. The form factor of an alternating current
waveform (signal) is the ratio of the RMS (Root Mean Square) value to the average
value (mathematical mean of absolute values of all points on the waveform). In
case of a sinusoidal wave, the form factor is 1.11.
§ The Main reason is something historical. In
olden days when the electricity becomes popular, the people had a misconception
that in the transmission line there would be a voltage loss of around 10%. So
in order to get 100 at the load point they started sending 110 from supply
side. This is the reason. It has nothing to do with form factor (1.11).
§ Nowadays that thought has changed and we are
using 400 V instead of 440 V, or 230 V instead of 220 V.
§ Also alternators are now available with terminal
voltages from 10.5 kV to 15.5 kV so generation in multiples of 11 does not
arise. Now a days when, we have voltage correction systems, power factor
improving capacitors, which can boost/correct voltage to desired level, we are
using the exact voltages like 400KV in spite of 444KV
4) What
is electrical corona?
§ Corona is the ionization of the nitrogen in the
air, caused by an intense electrical field.
§ Electrical corona can be distinguished from
arcing in that corona starts and stops at essentially the same voltage and is
invisible during the day and requires darkness to see at night.
§ Arcing starts at a voltage and stops at a voltage
about 50% lower and is visible to the naked eye day or night if the gap is
large enough (about 5/8″ at 3500 volts).
5) What
are the indications of electrical corona?
§ A sizzling audible sound, ozone, nitric acid (in
the presence of moisture in the air) that accumulates as a white or dirty
powder, light (strongest emission in ultraviolet and weaker into visible and
near infrared) that can be seen with the naked eye in darkness, ultraviolet
cameras, and daylight corona cameras using the solar-blind wavelengths on earth
created by the shielding ozone layer surrounding the earth.
6) What
damage does corona do?
§ The accumulation of the nitric acid and
micro-arcing within it create carbon tracks across insulating materials. Corona
can also contribute to the chemical soup destruction of insulating cements on
insulators resulting in internal flash-over.
§ The corona is the only indication. Defects in
insulating materials that create an intense electrical field can over time
result in corona that creates punctures, carbon tracks and obvious
discoloration of NCI insulators.
7) How
long does corona require creating visible damage?
§ In a specific substation the corona ring was
mistakenly installed backwards on a temporary 500kV NCI insulator, at the end
of two years the NCI insulator was replaced because 1/3 of the insulator was
white and the remaining 2/3 was grey.
8) What
voltage are corona rings typically installed at?
§ It varies depending upon the configuration of
the insulators and the type of insulator, NCI normally start at 160kV, pin and
cap can vary starting at 220kV or 345kV depending upon your engineering
tolerances and insulators in the strings.
9) How
do we select transformers?
§ Determine primary voltage and frequency.
§ Determine secondary voltage required.
§ Determine the capacity required in volt-amperes.
This is done by multiplying the load current (amperes) by the load voltage
(volts) for single phase.
§ For example: if the load is 40 amperes, such as
a motor, and the secondary voltage is 240 volts, then 240 x 40 equals 9600 VA.
A 10 KVA (10,000 volt-amperes) transformer is required.
§ Always select Transformer Larger than Actual
Load. This is done for safety purposes and allows for expansion, in case more
loads is added at a later date. For 3 phase KVA, multiply rated volts x load
amps x 1.73 (square root of 3) then divide by 1000.
§ Determine whether taps are required. Taps are
usually specified on larger transformers.
10) Why
Small Distribution Transformers not used for Industrial Applications?
§ Industrial control equipment demands a momentary
overload capacity of three to eight times’ normal capacity. This is most
prevalent in solenoid or magnetic contactor applications where inrush currents
can be three to eight times as high as normal sealed or holding currents but
still maintain normal voltage at this momentary overloaded condition.
§ Distribution transformers are designed for good
regulation up to 100 percent loading, but their output voltage will drop
rapidly on momentary overloads of this type making them unsuitable for high
inrush applications.
§ Industrial control transformers are designed
especially for maintaining a high degree of regulation even at eight time’s
normal load. This results in a larger and generally more expensive transformer.
11) Can 60 Hz
transformers be used at higher frequencies?
§ Transformers can be used at frequencies above 60
Hz up through 400 Hz with no limitations provided nameplate voltages are not
exceeded.
§ However, 60 Hz transformers will have less
voltage regulation at 400 Hz than 60 Hz.
12) What is meant
by regulation in a transformer?
§ Voltage regulation in transformers is the
difference between the no load voltage and the full load voltage. This is
usually expressed in terms of percentage.
§ For example: A transformer delivers 100 volts at
no load and the voltage drops to 95 volts at full load, the regulation would be
5%. Distribution transformers generally have regulation from 2% to 4%,
depending on the size and the application for which they are used.
13) Why is impedance
important?
§ It is used for determining the interrupting
capacity of a circuit breaker or fuse employed to protect the primary of a
transformer.
§ Example: Determine a minimum circuit breaker trip rating and interrupting
capacity for a 10 KVA single phase transformer with 4% impedance, to be
operated from a 480 volt 60 Hz source.
§ Calculate:
§ Normal Full Load Current = Nameplate Volt Amps /
Line Volts = 10,000 VA / 480 V = 20.8 Amperes
§ Maximum Short Circuit Amps = Full Load Amps / 4%
=20.8 Amps / 4%= 520 Amp
§ The breaker or fuse would have a minimum
interrupting rating of 520 amps at 480 volts.
§ Example: Determine the interrupting capacity, in amperes, of a circuit
breaker or fuse required for a 75 KVA, three phase transformer, with a primary
of 480 volts delta and secondary of 208Y/120 volts. The transformer impedance
(Z) = 5%. If the secondary is short circuited (faulted), the following
capacities are required:
§ Normal Full Load Current =Volt Amps / √ 3 x Line
Volts= 75,000 VA / √ 3 x Line Volts √ 3 x 480 V =90 Amps
§ Maximum Short Circuit Line Current = Full Load
Amps / 5%= 90 Amps / 5% =1,800 Amps
§ The breaker or fuse would have a minimum
interrupting rating of 1,800 amps at 480 volts.
§ Note: The secondary voltage is not used in the calculation. The reason
is the primary circuit of the transformer is the only winding being
interrupted.
14) What causes
flash-over?
§ Flash-over causes are not always easily
explained, can be cumulative or stepping stone like, and usually result in an
outage and destruction. The first flash-over components are available voltage
and the configuration of the energized parts, corona may be present in many
areas where the flash-over occurs, and flash-over can be excited by stepping
stone defects in the insulating path.
15) What are taps
and when are they used?
§ Taps are provided on some transformers on the
high voltage winding to correct for high or low voltage conditions, and still
deliver full rated output voltages at the secondary terminals. Taps are
generally set at two and a half and five percent above and below the rated
primary voltage.
16) Can
Transformers be reverse connected?
§ Dry type distribution transformers can be
reverse connected without a loss of KVA rating, but there are certain
limitations. Transformers rated 1 KVA and larger single phase, 3 KVA and larger
three phases can be reverse connected without any adverse effects or loss in
KVA capacity.
§ The reason for this limitation in KVA size is,
the turns ratio is the same as the voltage ratio.
§ Example: A transformer with a 480 volt input,
240 volt output— can have the output connected to a 240 volt source and thereby
become the primary or input to the transformer, then the original 480 volt
primary winding will become the output or 480 volt secondary.
§ On transformers rated below 1 KVA single phase,
there is a turn’s ratio compensation on the low voltage winding. This means the
low voltage winding has a greater voltage than the nameplate voltage indicates
at no load.
§ For example, a small single phase transformer
having a nameplate voltage of 480 volts primary and 240 volts secondary, would
actually have a no load voltage of approximately 250 volts, and a full load
voltage of 240 volts. If the 240 volt winding were connected to a 240 volt
source, then the output voltage would consequently be approximately 460 volts
at no load and approximately 442 volts at full load. As the KVA becomes
smaller, the compensation is greater—resulting in lower output voltages.
§ When one attempts to use these transformers in
reverse, the transformer will not be harmed; however, the output voltage will
be lower than is indicated by the nameplate.
17) What is the
difference between “Insulating”, “Isolating”, and “Shielded Winding”
transformers?
§ Insulating and isolating transformers are
identical. These terms are used to describe the separation of the primary and
secondary windings. A shielded transformer includes a metallic shield between
the primary and secondary windings to attenuate (lessen) transient noise.
18) How many BTU’s
of heat does a transformer generate?
§ The heat a transformer generates is dependent
upon the transformer losses. To determine air conditioning requirements
multiply the sum of the full load losses (obtained from factory or test report)
of all transformers in the room by 3.41 to obtain the BTUs/hour.
For example: A transformer with losses of 2000 watts will generate 6820 BTUs/hour.
For example: A transformer with losses of 2000 watts will generate 6820 BTUs/hour.
19) What is a
transformer and how does it work?
§ A transformer is an electrical apparatus
designed to convert alternating current from one voltage to another. It can be
designed to “step up” or “step down” voltages and works on the magnetic
induction principle.
§ A transformer has no moving parts and is a
completely static solid state device, which insures, under normal operating
conditions, a long and trouble-free life. It consists, in its simplest form, of
two or more coils of insulated wire wound on a laminated steel core.
§ When voltage is introduced to one coil, called
the primary, it magnetizes the iron core. A voltage is then induced in the
other coil, called the secondary or output coil. The change of voltage (or
voltage ratio) between the primary and secondary depends on the turns ratio of
the two coils.
20) Factors
Affecting Corona Discharge Effect:
§ Corona Discharge Effect occurs because of
ionization if the atmospheric air surrounding the voltage conductors, so Corona
Discharge Effect is affected by the physical state of the atmosphere as well as
by the condition of the lines.
§ (1) Conductor: Corona Discharge Effect is
considerably affected by the shape, size and surface conditions of the
conductor .Corona Discharge Effect decreases with increases in the size
(diameter) of the conductor, this effect is less for the conductors having
round conductors compared to flat conductors and Corona Discharge Effect is concentrated
on that places more where the conductor surface is not smooth.
§ (2) Line Voltage: Corona Discharge effect is not present when the
applied line voltages are less. When the Voltage of the system increases (In
EHV system) corona Effect will be more.
§ (3) Atmosphere: Breakdown voltage directly proportional to the
density of the atmosphere present in between the power conductors. In a stormy
weather the ions present around the conductor is higher than normal weather
condition So Corona Breakdown voltage occurs at low voltages in the stormy
weather condition compared to normal conditions
§ (4)Spacing between the Conductors: Electro static stresses are reduced with
increase in the spacing between the conductors. Corona Discharge Effect takes
place at much higher voltage when the distance between the power conductors
increases.
21) Will a
transformer change Three Phases to Single Phase?
§ A transformer will not act as a phase changing
device when attempting to change three phase to single phase.
§ There is no way that a transformer will take
three phase in and deliver single phase out while at the same time presenting a
balanced load to the three phase supply system.
§ There are, however, circuits available to change
three phase to two phase or vice versa using standard dual wound transformers.
Please contact the factory for two phase applications.
22) Can 60 Hz
transformers be operated at 50 Hz?
§ Transformers rated below 1 KVA can be used on 50
Hz service.
§ Transformers 1 KVA and larger, rated at 60 Hz,
should not be used on 50 Hz service, due to the higher losses and resultant
heat rise. Special designs are required for this service. However, any 50 Hz
transformer will operate on a 60 Hz service.
23) Can
transformers be used in parallel?
§ Single phase transformers can be used in
parallel only when their impedances and voltages are equal. If unequal voltages
are used, a circulating current exists in the closed network between the two
transformers, which will cause excess heating and result in a shorter life of
the transformer. In addition, impedance values of each transformer must be
within 7.5% of each other.
§ For example: Transformer A has an impedance of
4%, transformer B which is to be parallel to A must have impedance between the
limits of 3.7% and 4.3%. When paralleling three phase transformers, the same
precautions must be observed as listed above, plus the angular displacement and
phasing between the two transformers must be identical.
24) What are causes
of insulator failure?
§ Electrical field intensity producing corona on
contaminated areas, water droplets, icicles, corona rings, … This corona
activity then contributes nitric acid to form a chemical soup to change the
bonding cements and to create carbon tracks, along with ozone and ultraviolet
light to change the properties of NCI insulator coverings. Other detrimental
effects include water on the surface or sub-surface freezing and expanding when
thawing, as a liquid penetrating into a material and then a sudden temperature
change causes change of state to a gas and rapid expansion causing fracture or
rupture of the material.
25) Causes of
Corona
§ Corona is causes by the following reasons:
§ The natural electric field caused by the flow of
electrons in the conductor. Interaction with surrounding air.
Poor or no insulation is not a major cause but increases corona.
Poor or no insulation is not a major cause but increases corona.
§ The use of D.C (Direct Current) for
transmission.(Reason why most transmission is done in form of AC)
26) Effects of
Corona
1)
Line Loss – Loss of energy because some energy is used up to cause vibration of
the air particles.
2)
Long term exposure to these radiations may not be good to health (yet to be
proven).
3)
Audible Noise
4)
Electromagnetic Interference to telecommunication systems
5)
Ozone Gas production
6)
Damage to insulation of conductor.
27) What is
polarity, when associated with a transformer?
§ Polarity is the instantaneous voltage obtained
from the primary winding in relation to the secondary winding.
§ Transformers 600 volts and below are normally
connected in additive polarity — that is, when tested the terminals of the high
voltage and low voltage windings on the left hand side are connected together,
refer to diagram below. This leaves one high voltage and one low voltage
terminal unconnected.
§ When the transformer is excited, the resultant
voltage appearing across a voltmeter will be the sum of the high and low
voltage windings.
§ This is useful when connecting single phase
transformers in parallel for three phase operations. Polarity is a term used
only with single phase transformers.
28) What is
exciting current?
§ Exciting current, when used in connection with
transformers, is the current or amperes required for excitation. The exciting
current on most lighting and power transformers varies from approximately 10%
on small sizes of about 1 KVA and smaller to approximately .5% to 4% on larger
sizes of 750 KVA. The exciting current is made up of two components, one of
which is a real component and is in the form of losses or referred to as no
load watts; the other is in the form of reactive power and is referred to as
KVAR.
29) What is
Boucholz relay and the significance of it in to the transformer?
§ Boucholz relay is a device which is used for the
protection of transformer from its internal faults,
§ it is a gas based relay. whenever any internal
fault occurs in a transformer, the boucholz relay at once gives a horn for some
time, if the transformer is isolated from the circuit then it stop its sound
itself otherwise it trips the circuit by its own tripping mechanism.
30) Why we do two
types of earthing on transformer (Body earthing & neutral earthing)
§ The two types of earthing are Familiar as
Equipment earthing and system earthing.
§ In Equipment earthing: body (non conducting
part) of the equipment should be earthed to safeguard the human beings.
§ The System Earthing : In this neutral of the
supply source ( Transformer or Generator) should be grounded. With this, in
case of unbalanced loading neutral will not be shifted. So that unbalanced
voltages will not arise. We can protect the equipment also. With size of the equipment
( transformer or alternator)and selection of relying system earthing will be
further classified into directly earthed, Impedance earthing, resistive (NGRs)
earthing.
31) Conductor
corona is caused by?
§ Corona on a conductor can be due to conductor
configuration (design) such as diameter too small for the applied voltage will
have corona year-around and extreme losses during wet weather, the opposite
occurs during dry weather as the corona produces nitric acid which accumulates
and destroys the steel reinforcing cable (ACSR) resulting in the line dropping.
Road salts and contaminants can also contribute to starting this deterioration.
32) What is
flash-over and arcing?
§ Flash-over is an instantaneous event where the
voltage exceeds the breakdown potential of the air but does not have the
current available to sustain an arc, an arc can have the grid fault current
behind it and sustain until the voltage decreases below 50% or until a
protective device opens.
§ Flash-over can also occur due to induced
voltages in unbounded (loose bolts, washers, etc) power pole or substation
hardware, this can create RFI/TVI or radio/TV interference. Arcing can begin at
5 volts on a printed circuit board or as the insulation increases it may
require 80kVAC to create flash-over on a good cap and pin insulator.
33) How to
Minimizing Corona Effects
§ Installing corona rings at the end of
transmission lines.
§ A corona ring, also called anti-corona ring, is
a toroid of (typically) conductive material located in the vicinity of a
terminal of a high voltage device. It is electrically insulated.
§ Stacks of more spaced rings are often used. The
role of the corona ring is to distribute the electric field gradient and lower
its maximum values below the corona threshold, preventing the corona discharge.
34) What is BIL and
how does it apply to transformers?
§ BIL is an abbreviation for Basic Impulse Level.
Impulse tests are dielectric tests that consist of the application of a high
frequency steep wave front voltage between windings, and between windings and
ground. The Basic Impulse Level of a transformer is a method of expressing the
voltage surge (lightning, switching surges, etc.) that a transformer will
tolerate without breakdown.
§ All transformers manufactured in this catalog,
600 volts and below, will withstand the NEMA standard BIL rating, which is 10
KV.
§ This assures the user that he will not
experience breakdowns when his system is properly protected with lightning
arrestors or similar surge protection devices.
35) The difference
between Ground and Neutral?
§ NEUTRAL is the origin of all current flow. In a
poly-phase system, as its phase relationship with all the three phases is the
same, (i.e.) as it is not biased towards any one phase, thus remaining neutral,
that’s why it is called neutral.
§ Whereas, GROUND is the EARTH on which we stand.
It was perceived to utilize this vast, omnipresent conductor of electricity, in
case of fault, so that the fault current returns to the source neutral through
this conductor given by nature which is available free of cost. If earth is not
used for this purpose, then one has to lay a long. long metallic conductor for
the purpose, thus increasing the cost.
§ Ground should never be
used as neutral. The protection devices (eg ELCB, RCD etc) work basically on
principle that the phase currects are balanced with neutral current. In case
you use ground wire as the neutral, these are bound to trip if they are there –
and they must be there. at least at substations. And these are kept very
sensitive i.e. even minute currents are supposed to trip these.
§ One aspect is safety – when someone touches a
neutral, you don’t want him to be electrocuted – do you? Usually if you see the
switches at home are on the phase and not neutral (except at the MCB stage).
Any one assumes the once the switch is off, it is safe (the safety is taken
care of in 3 wire system, but again most of the fixtures are on 2 wire) – he
will be shocked at the accidental touching of wire in case the
floating neutral is floating too much.
36) What is
impedance of a transformer?
§ If you mean the percentage impedance of the
transformed it means the ratio of the voltage( that if you applied it to one
side of the transformer while the other side of the transformer is short
cuitcuted, a full load current shall flow in the short circuits side), to the
full load current.
§ More the %Z of transformer, more Copper used for
winding, increasing cost of the unit. But short circuit levels will reduce,
mechanical damages to windings during short circuit shall also reduce. However,
cost increases significantly with increase in %Z.
§ Lower %Z means economical designs. But short
circuit fault levels shall increase tremendously, damaging the winding &
core.
§ The high value of %Z helps to reduce short
circuit current but it causes more voltage dip for motor starting and more
voltage regulation (% change of voltage variation) from no load to full load.
37) How are
transformers sized to operate Three Phase induction type squirrel cage motors?
§ The minimum transformer KVA rating required to operate
a motor is calculated as follows:
§ Minimum Transformer KVA =Running Load Amperes x
1.73x Motor Operating Voltage / 1000
§ NOTE: If motor is to be started more than once per hour add 20%
additional KVA. Care should be exercised in sizing a transformer for an
induction type squirrel cage motor as when it is started, the lock rotor
amperage is approximately 5 to 7 times the running load amperage. This severe
starting overload will result in a drop of the transformer output voltage.
§ When the voltage is low the torque and the
horsepower of the motor will drop proportionately to the square of the voltage.
§ For example: If the voltage were to drop
to 70% of nominal, then motor horsepower and torque would drop to 70 % squared
or 49% of the motor nameplate rating.
§ If the motor is used for starting a high torque
load, the motor may stay at approximately 50% of normal running speed The
underlying problem is low voltage at the motor terminals. If the ampere rating
of the motor and transformer over current device falls within the motor’s 50%
RPM draw requirements, a problem is likely to develop. The over current device
may not open under intermediate motor ampere loading conditions.
§ Overheating of the motor and/or transformer
would occur, possibly causing failure of either component.
§ This condition is more pronounced when one
transformer is used to power one motor and the running amperes of the motor is
in the vicinity of the full load ampere rating of the transformer. The
following precautions should be followed:
§ (1)When one transformer is used to operate one motor, the running
amperes of the motor should not exceed 65% of the transformer’s full load
ampere rating.
§ (2) If several motors are being operated from one transformer, avoid
having all motors start at the same time. If this is impractical, then size the
transformer so that the total running current does not exceed 65% of the
transformer’s full load ampere rating.
38) Which Point
need to be consider while Neutral Earthing of Transformer?
§ The following points need to check before going
for Neutral Grounding Resistance.
§ Fault current passing through ground, step and
touch potential.
§ Capacity of transformer to sustain ground fault
current, w.r.t winding, core burning.
§ Relay co-ordination and fault clearing time.
§ Standard practice of limiting earth fault
current. In case no data or calculation is possible, go for limiting E/F
current to 300A or 500A, depending on sensivity of relay.
39) Why a neutral
grounding contactor is needed in diesel generator?
§ There would not be any current flow in neutral
if DG is loaded equally in 3 phases , if there any fault(earth fault or over
load) in any one of the phase ,then there will be un balanced load in DG . at
that time heavy current flow through the neutral ,it is sensed by CT and trips
the DG. so neutral in grounded to give low resistance path to fault current.
§ An electrical system consisting of more than two
low voltage Diesel Generator sets intended for parallel operation shall meet
the following conditions:
§ (i) Neutral of only one generator needs to be
earthed to avoid the flow of zero sequence current.
§ (ii) During independent operation, neutrals of
both generators are required in low voltage switchboard to obtain three phases,
4 wire system including phase to neutral voltage.
§ (iii) required to achieve restricted earth fault
protection (REF) for both the generators whilst in operation.
§ Solution:
§ Considering the requirement of earthing neutral
of only one generator, a contactor of suitable rating shall be provided in
neutral to earth circuit of each generator. This contactor can be termed as
“neutral contactor”.
§ Neutral contactors shall be interlocked in such
a way that only one contactor shall remain closed during parallel operation of
generators. During independent operation of any generator its neutral contactor
shall be closed.
§ Operation of neutral contactors shall be
preferably made automatic using breaker auxiliary contacts.
40) Neutral
grounded system vs solidly grounded system
§ In India, at low voltage level (433V) we MUST do
only Solid Earthing of the system neutral.
§ This is by IE Rules 1956, Rule No. 61 (1) (a).
Because, if we option for impedance earthing, during an earth fault, there will
be appreciable voltage present between the faulted body & the neutral, the
magnitude of this voltage being determined by the fault current magnitude and
the impedance value.
§ This voltage might circulate enough current in a
person accidentally coming in contact with the faulted equipment, as to harm
his even causing death. Note that, LV systems can be handled by non-technical
persons too. In solid earthing, you do not have this problem, as at the instant
of an earth fault, the faulted phase goes to neutral potential and the high
fault current would invariably cause the Over current or short circuit
protection device to operate in sufficiently quick time before any harm could
be done
Comments
Post a Comment