Electrical Q&A Part-3
1) What
is the reason of grounding or earthing of equipment?
§ with a ground path, in case of short circuit the
short circuit current goes to the body of the equipment & then to the
ground through the ground wire. Hence if at the moment of fault if a person
touches the equipment body he will not get a shock cause his body resistance
(in thousands of ohms) will offer a high resistance path in comparison to the
ground wire. Hence the fault current will flow thru the ground wire & not
thru human body.
§ Providing a ground path helps in clearing the
fault. A CT in the ground connection detects the high value fault current hence
the relay connected to the CT gives breaker a trip command.
§ Grounding helps in avoiding arcing faults. IF
there would have been no ground then a fault with the outer body can cause a
arcing to the ground by breaking the air. This is dangerous both for the
equipment & the human beings.
2) A
type-C MCB has thermo magnetic capability 5In to 10In that means a short
circuit current will be interrupted as the value will reach between 5In to 10In
but the MCB breaking capacity is (for example) define as 10kA.
§ 5In to 10In is the pickup threshold for the
magnetic trip element. The MCB will trip instantaneously when the current is
between these limits. 10kA is the short circuit withstands capacity of the MCB.
§ Under normal condition, a current limiting type
MCB will trip on short circuit (magnetic trip) and the current during circuit
interruption will be much less than the prospective current. However, the MCBs
have to have a short circuit capacity more than or equal to the fault level at
the location where it is installed.
3) What
is Ferrari Effect?
§ Ferranti Effect is due to the rise in voltage at
the receiving end than that of the sending end. This occurs when the load on
the system reduces suddenly.
§ Transmission line usually consists of line
inductance, line to earth capacitance and resistance. Resistance can be
neglected with respect to the line inductance .When the load on the system falls
the energy stored in the capacitance gets discharged. The charging current
causes inductive reactance voltage drop. This gets added vector ally to the
sending end voltage and hence causes the voltage at the receiving end to raise
§ A Long transmission line draws significant
amount of charging current. If such line is open circuited or very lightly
loaded at the receiving end, the voltage at the receiving end may become
greater than sending end voltage. This effect is known Ferranti effect and is
due to the voltage drop across the line inductance (due to charging current)
being in phase with the sending end voltages. Therefore both capacitance and
inductance is responsible to produce this phenomenon.
§ The capacitance (charging current) is negligible
in short lines, but significant in medium and long transmission line. Hence,
this phenomenon is applicable for medium and long transmission line.
The main impact of this phenomenon is on over voltage protection system, surge protection system, insulation level etc.
The main impact of this phenomenon is on over voltage protection system, surge protection system, insulation level etc.
4) Can
single phase transformers be used for three phase applications?
§ Yes. Three phase transformers are sometimes not
readily available whereas single phase transformers can generally be found in
stock. Three single phase transformers can be used in delta connected primary
and wye or delta connected secondary. They should never be connected wye
primary to wye secondary, since this will result in unstable secondary voltage.
The equivalent three phase capacity when properly connected of three single phase
transformers is three times the nameplate rating of each single phase
transformer.
5) What
is BIL and how does it apply to transformers?
§ BIL is an abbreviation for Basic Impulse Level.
Impulse tests are dielectric tests that consist of the application of a high
frequency steep wave front voltage between windings, and between windings and
ground. The BIL of a transformer is a method of expressing the voltage surge
that a transformer will tolerate without breakdown.
6) Where Auto-recloser is
used?
§ For Generator protection / Transformer
Protection / Transmission Line / Bus bar protection.
§ Many faults on overhead transmission lines are
transient in nature 90% of faults are used by birds, tree branches. These
condition results in arching faults and the arc in the fault can be
extinguished by de-energizing the lines by opening of CB on the both ends of
the lines.
§ Open-0.3 second-Close-3minute-Close this is the
sequence of AR. i.e.-OPEN,C-CLOSED
§ whenever faults occurs CB opens, then after 0.3
sec it closes automatically, if faults persists then it will open after 3 min
it closes and if still fault persists. It remains in open condition.
§ Auto reclosure is generally used for
Transmission lines where the general types of faults are transient in nature.
§ It can be three phase auto-reclosure or single
pole auto-reclosure.
§ The single pole auto reclosures are generally
for 400kV line below this three pole auto- reclosures are used.
§ The reason for a line the single pole reclosures
provides a better stability of the system since some part of power is still
transferred through the healthy phases.
§ Also 400kV breaker till date has a independent
drive/ trip/ close coils for the three poles, below that all breakers have
common drive/ trip / closing coils for the three poles.
7) What
is difference between power transformers & distribution transformers?
§ Distribution Transformers are designed for a
maximum efficiency at 50% of load. Whereas power transformers are designed to
deliver max efficiency ay 90% and above loads.
§ The distributions transformers have low
impedance so as to have a better regulation power transformers have higher so
as to limit the SC current.
§ Power transformers are used to step up voltages
from 11 KV which is the generating voltage to 132 or whatever will be the
transmission voltage levels. Power transformers are having Star-Delta
connection. It will be located at power generating stations.
§ Distribution transformers are used to step down
voltages from transformer levels to 11 KV/415 V. Will be having Delta-Star. It
will be located in substations near load centers.
§ The main basic difference lies in the Design
stage itself as power transformer are to operate at near full load so there
sensing is such that they achieve equal. of copper losses & iron losses at full
loads whereas this is achieved in the design itself at about 50% loading in
dist transformer but friends there is a dilemma as our dist. transformer are
almost fully loaded & beyond so they never go operate at their full eff.
& also poor voltage regulation.
§ The difference between power and distribution
transformers refers to size & input voltage. Distribution transformers vary
between 25 kVA and 10 MVA, with input voltage between 1 and 36 kV. Power
transformers are typically units from 5 to 500 MVA, with input voltage above 36
kV. Distribution transformer design to have a max efficiency at a load lower
than full load. Power transformer design to have a max efficiency at full load
8) What
will be happen if the neutral isolator will be open or close during the running
condition of power?
§ During normal condition the neutral isolating
switch should be kept close. In case it is kept open, under balanced load
conditions the current through neutral will not flow & nothing harmful will
take place but in case an earth fault takes place then there will be no earth
fault current flowing through the system & the generator will run as a
ungrounded generator. Thus the earth fault will not be cleared.
§ If more number of generators are connected
parallel. We will have a close loop and hence negative sequence current will
flow. This will increase the rotor temperature. Hence if more number of
generators are connected then only one is earthed and others are open.
§ In case of Two or more generators connected to a
common bus without a transformer in between, basically in hydro stations, one
of the Neutral Isolation Switch(NIS) is kept closed & rest are opened to
prevent circulating currents to flow between generators. Hence the above
explanation will not be valid for such systems.
§ Sometime we may want to test generator and may
want to isolate the neutral from ground. like for example meggaring etc. In
such case we would like to open ground connection cable in case we want to
remove the NIS? we will certainly not like to open all the bolted connections
for just a small test like checking insulation with a meggar etc. for such
things we need a NIS.
§ Neutral isolator is required if we have delta
transmission system and at the time to connection with the Grid Neutral
isolation is required.
§ If we ungrounded the neutral then the generator
is connected to the ground via Phase to earth capacitances. Hence during faults
arcing grounds can take place. Which are dangerous both to human &
equipment.
§ When we provide earthed neutral, for a fault,
earth fault current will start flowing through the neutral, which we can sense
thru a CT & relay & hence can immediately identify & clear the
fault in about 100 ms by opening the associated breaker/prime mover/excitation.
Quicker the fault clearance less is the damage.
9) Why
shorting type terminal required for CT?
§ During maintenance or secondary injection you
will need to bypass the CT & for the same you need shorting link. During
sec. injection you will short circuit the main CT & bypass it. Open
circuiting the CT will saturate it & damage it.
10) Why fuse is
given for only PT and not CT?
§ Fuse if given for CT blows off due to a fault
then rather than protecting the CT it will make it open circuited hence it will
be saturated & damaged. For PT it gives overload & SC protection.
11) Why is
insulating base required for LA?
§ The LA is provided with a dedicated Prper
earthing which may be in the form of a buried treated electrode next
to it.LA connection is securely made with the electrode via a surge
counter. If we directly earth the LA through structure then the surge counter
will not be able to measure the no of surges. For lesser rating the counter is
not provided, hence we can bypass the insulated base. But then proper earthing
has to be assured.
12) Can 60 Hz
transformers be operated at 50 Hz?
§ Transformers 1 KVA and larger, rated at 60 Hz,
should not be used on 50 Hz service due to higher losses and resultant heat
rise. However, any 50 Hz transformer will operate on 60 Hz service.
13) Can transformers
be used in parallel?
§ Single phase transformers can be used in
parallel only when their voltages are equal. If unequal voltages are used, a
circulating current exists in the closed network between the two transformers
which will cause excess heating and result in a shorter life of the
transformer. In addition impedance values of each transformer must be within
7.5% of each other.
14) Can Transformers
be reverse connected?
§ Dry type distribution transformers can be
reverse connected without a loss of KVA rating, but there are certain
limitations. Transformers rated 1 KVA and larger single phase, 3 KVA and larger
three phases can be reverse connected without any adverse effects or loss in
KVA capacity.
15) Why short
circuit do not take place when electrode is touched to ground.
§ Basically during welding we force a
short-circuit at the electrode tip. The fault condition produces large
magnitude currents. Greater the Current value have greater I2R heat produced.
The arcing energy elevates the temperature & hence melts the electrode
material over the joint.
§ The transformer is designed to withstand such
high currents. But welding is a very complex & detailed phenomenon. Besides
there are many principles on which welding operates. Some may be a welding, dc welding,
arc, constant voltage, constant current etc
16) What’s the
difference between generator breaker and simple breaker?
§ Breaker is one which disconnects the circuit in
fault condition and It is similar for all equipment. Based on the equipment
voltage and maximum short circuit current the ratings will be decided. For
better understanding we call generator or transformer or line etc breakers.
17) What is accuracy
Class of the instrument?
§ Generally the class indicates the accuracy with
which the meter will indicate or equipment will measure with respect to its
input.
§ The accuracy of different equipment will depend
on number of factors.
§ For example for a PT accuracy will depend
on its leakage reactance & winding resistance. For a PT accuracy gives the
voltage & phase error & it varies with the VA burden of secondary. Also
better core material will give better heat dissipation & reduce error.
class of accuracy will give the voltage error for a PT
§ different type of PTs available are:0.1, 0.2,
0.5, 1, 5 & error values will be: class% voltage error(+/_) phase
displacement
Similarly indicating instruments shall have accuracies & accordingly application as depicted below for testing the following values are generally used:
Similarly indicating instruments shall have accuracies & accordingly application as depicted below for testing the following values are generally used:
§ for routine tests : accuracy class 1
§ for type tests : accuracy class 0.5 or better.
§ indicating meters generally will have accuracy
of 1.
18) First pole to
clear factor-Circuit breakers
§ The first pole to clear factor (kpp) is depending
on the earthing system of the network. The first pole to clear factor is used
to calculating the transient recovery voltage for three phase faults. In
general following cases apply:-
1. kpp = 1.3 corresponds to three phase faults in system with an earthed neutral.
2. kpp = 1.5 corresponds to three phase faults in isolated or resonant earthed system.
3. kpp = 1.0 corresponds to special cases e.g. railway systems.
1. kpp = 1.3 corresponds to three phase faults in system with an earthed neutral.
2. kpp = 1.5 corresponds to three phase faults in isolated or resonant earthed system.
3. kpp = 1.0 corresponds to special cases e.g. railway systems.
§ A special case is when there is a three phase
fault without involving earth in a system with earthed neutral. This case
responds to kpp = 1.5 . This special case is however not normally considered in
the standards.
19) Why we use a
resistance to ground the neutral when we need always low resistivity for the
grounding?
§ If we ground the generator directly then
whenever a fault will take place at any phase with ground the fault current
flowing throw the faulted phase-to ground-to neutral will be very high cause
there will be no resistance to limit the value of fault current. Hence we
insert a resistance in the neutral circuit to limit this fault current. Also we
need to reduce the fault current to such a value that the protection CTs are
able to identify the fault current without saturating the CTs. Communicate it
to the protection relays & hence the relays can then isolate the system
from the fault; so that the system is isolated from the fault before the harm
is done by the fault current. That is the reason that all the equipment will be
designed for fault KA values for 1 sec so that the total operation(CT
sensing-relay functioning-circuit breaker operation ) time will be less than 1
sec. hence the Breakers will isolate the fault before 1 sec i.e. within the
time period the equipment are designed to carry the fault current. Thus all
your objectives of:
§ preventing the arcing.
§ limiting the fault current.
§ isolating the faulted system are achieved
20) Why are NGR’s
rated for 10sec?
§ NGR are placed in the neutral circuit &
hence will be energized only in the fault conditions thus their continuous
loading is not expected. Hence they are selected for intermittent rating.
Similarly when we place a transformer in the neutral grounding circuit the KVA
rating obtained after the calculation is multiplied by a diversity factor to
obtain smaller rating cause the therefore It will not be continuously rated.
§ NIS is also provided to cut the circulating
negative sequence current in 2 more generators connected in parallel.
in some grid conditions they ask to keep neutral isolated after being connected to grid.
in some grid conditions they ask to keep neutral isolated after being connected to grid.
21) How to calculate
knee point voltage and significance of knee point voltage?
§ Knee point voltage: That point on the
magnetizing curve (BH curve) where an increase of 10% in the flux density
(voltage) causes an increase of 50% in the magnetizing force (current). Its
significance lies mainly in PS class core of CTs used for diff protection
22) Design method
for neutral grounding resistor?
§ NGR design basics:
§ Capacitive coupling of generator, equipment and
the ground
-Generator to ground capacitance.
-Generator cable to ground capacitance (or bus duct as the case may be)
-Low voltage winding of trafo & ground capacitance.
-Surge arrestor capacitance.
-Generator to ground capacitance.
-Generator cable to ground capacitance (or bus duct as the case may be)
-Low voltage winding of trafo & ground capacitance.
-Surge arrestor capacitance.
§ The total capacitance is then obtained from the
above values & then we calculate from that the capacitive reactance. The
capacitive current then produced is calculated from the generator voltage &
the capacitive reactance obtained above. Once the current is obtained we can
then calculate the electrostatic KVA from the current multiplied with voltage.
23) Criterion is
there for selection of Insulation Disc in Transmission and Distribution Line.
§ 11kV is the phase to earth voltage for 220kV
=220/ (sqrt(3)*11)=12 No’s of disc are suitable.The number can be
increased to increase the creep age distance.
§ While selecting the disc insulators one has to
keep in mind the following things:
1. EM-strength of the string. All the forces coming on to the string & the ability of the string to withstand them.
2. Sufficient Cree page distance so as not to cause a flashover .
3. Interface with the type of conductor used (moose, tarantula, zebra etc)
1. EM-strength of the string. All the forces coming on to the string & the ability of the string to withstand them.
2. Sufficient Cree page distance so as not to cause a flashover .
3. Interface with the type of conductor used (moose, tarantula, zebra etc)
§ So we will get the value of no of discs by
dividing the phase to earth voltage with 1.732. Once that is done then we need
to see its suitability with respect to EM strength.
§ After this we need to consider the force that
the stack has to bear. If we have a strain type of fitting i.e. the stack has
to bear horizontal conductor tension, weight load of the conductor, wind load,
ice load etc then the number of insulator discs required may be more.
§ But for a suspension type system which has to
bear only the weight then number of discs required may be less than what we get
by dividing by 11. That is the reason we have seen only 23/24 discs in 400 kv
line cause in that case the creep age obtained must have been enough & also
the strain requirement.
§ 33kv insulators are generally used in a vertical
installation & are not stacked together because that will make the
suspension very rigid
24) Do taps work the
same when a transformer is reverse fed?
§ Taps are normally in the primary winding to
adjust for varying incoming voltage. If the transformer is reverse fed, the
taps are on the output side and can be used to adjust the output voltage.
25) Why may I get
the wrong output voltage when installing a step up transformer?
§ Transformer terminals are marked according to
high and low voltage connections. An H terminal signifies a high voltage
connection while an X terminal signifies a lower voltage connection. A common
misconception is that H terminals are primary and X terminals secondary. This
is true for step down transformers, but in a step up transformer the
connections should be reversed. Low voltage primary would connect to X terminals
while high voltage secondary would connect on the H terminals.
26) Can a single
phase transformer be used on a three phase source?
§ Yes. Any single phase transformer can be used on
a three phase source by connecting the primary leads to any two wires of a
three phase system, regardless of whether the source is three phase 3-wire or
three phase 4-wire. The transformer output will be single phase.
27) Why in Double
circuit wire are transposed (R – B, Y – Y, B – R)
§ This is done to avoid
1. Proximity effect
2. Skin effect
3. Radio interference
4. Reduction in noise in communication Signals
1. Proximity effect
2. Skin effect
3. Radio interference
4. Reduction in noise in communication Signals
28) Selection of LA
§ The voltage rating of LA is selected as: Line
voltage x sqrt(2)/ sqrt(3) so for 11kV line its 9kV
§ In that case also the values would not differ
much if We takes the TOV factor as 1.4. However, we can take the value of 1.56
as TOV to be more precise.
29) Which is more
dangerous AC or DC
§ Low frequency (50 – 60 Hz) AC currents can be
more dangerous than similar levels of DC current since the alternating
fluctuations can cause the heart to lose coordination, inducing ventricular
fibrillation, which then rapidly leads to death.
§ However any practical distribution system will
use voltage levels quite sufficient to ensure a dangerous amount of current
will flow, whether it uses alternating or direct current. Since the precautions
against electrocution are similar, ultimately, the advantages of AC power
transmission outweighed this theoretical risk, and it was eventually adopted as
the standard.
30) What all are the
applications where high speed grounding switches are used.
§ Generator neutral is earthed directly or through
distribution transformer. This neutral earthing is through done through a
switch. This is general practice for only one generator.
§ For two generators in parallel to a bus the
neutral earthing is different. If both the neutral earthing is closed the
negative sequence current will be flowing though both the generator taking
earth as path. This leads to increase in loss and increase in temperature (This
may leads to false tripping also). Hence once the second generator is
synchronized with the bus or grid the neutral is isolated.
§ Neutral grounding switch we do not need a high
speed grounding switch. A normal switch with the correct rating capacity would
also work.
31) What is Skin
Effect and how does it happen??
§ According to faradays law of electromagnetic
induction, a conductor placed in a changing magnetic field induces an emf. The
effect of back emf is maximum at the centre because of maximum lines of field
there. Hence the maximum opposition of current at inner side of conductor and
minimum opposition at the surface. Hence the current tries to follow at the
surface. It is due to this reason that we take hollow tube conductors in bus
duct.
§ Taking into account the inductance effect, its
simple consider the DC current. Since its constant & not varying hence no
back emf but if we gradually start increasing the frequency then the flux
cutting the conductor goes on increasing, hence greater the frequency greater
the alternating flux cutting the conductor & hence greater the back emf
& therefore greater the skin effect.
32) Why we ground
the sheath of single core power cables and to avoid grounded at both the ends?
§ A single core cable with a sheath is nothing but
a conductor carrying current surrounded by another conductor (sheath). Hence
the Alternative current in the conductor induces voltages in the sheath or the
armour. Hence grounding these cables at both ends will cause the potential of
the armour to be same as ground potential & hence shall become safe for the
personnel.
§ But grounding the cables at both the end will
cause a problem. In that case the circulating currents will start flowing with
the armor, the ground & with the two ends of the grounding completing the
circuit. This will also provide path for the fault currents to flow. Hence this
whole thing will cause the cable to produce some I2R losses, hence heating
& hence the current carrying capacity will be de rated. This system of
cable earthing is called both-end bonding. This system is suggested only when
one wants to avoid the voltage development because can either go with the de
rated cable or if one updates the cable in advance.
§ When only one end of the cable sheath is
grounded then there is no path for the circulating current to flow. Hence the
current carrying capacity of the cable will be good. But in this case potential
will be induced between sheath & ground. This potential is proportional to
the length of the cable & hence this will limit the length of the cable
used. This method is called single point bonding. This is thus used only for
short lengths.
§ There is another system called the cross bonding
system in which the sheath are sectionaliosed & cross connected so that the
circulating currents are minimized. Although some potential will also exist
between sheath & ground, the same being maximum at the link boxes where
bonding is done. This method provides maximum possible current carrying
capacity with the maximum possible lengths.
33) What is EDO
& MDO type breaker?
§ In the Breakers for the operation spring
charging is must.
§ In EDO breaker the spring charging is done with
a motor and draw out manually by hand. so EDO means Electrically spring charged
Draw Out breaker
§ In MDO breaker the spring charging is also done
by hand manually and draw out about also by hand only. so MDO means Manual
spring charge Draw Out breaker
34) Why transformer
rating is in KVA or KW?
§ Because power factor of the load is not defined
in case of transformer that’s why it is not possible to rate transformer in KW.
§ The losses (cu loss and iron loss) of the
transformer depends on current and voltage purely, not on load i.e, phase angle
between the current and voltage i.e. why transformer rated in kVA
§ Transformer is not a load and having no effect
on P.F (that’s why no change in its power factor) and it only transfer the
constant power from one voltage level to another voltage level without changing
frequency. since both the losses viz copper loss(depends on current) and iron
loss(depends on voltage) are independent of power factor, that is why a
Transformers rating is not on kW, but on KVA
35) Why the
secondary of CT never open when burden is connected on the CT.?
§ secondary of CT is never opened as because CT is
always connected to the line so opening the secondary will mean there will be
no counter mmf to balance the primary current as a result of which a very high
induced emf may appear in the secondary as flux is very high and no counter mmf
and this will be dangerous for the personnel in the secondary side and for pt
if it is shorted then with full voltage applied to the primary.
§ If we short the secondary then much high current
will circulate in the secondary due to high induced emf much higher than the
actual full load current as a result of which the transformer’s secondary
winding may burn out.
36) Distance relay
setting
§ Step1:
Get the conductor Details (i.e Positive Sequence Impedance (Z), Zero Sequence Impedance(Z0)) which is in Primary value. Convert in terms of secondary values.
Get the conductor Details (i.e Positive Sequence Impedance (Z), Zero Sequence Impedance(Z0)) which is in Primary value. Convert in terms of secondary values.
§ Step 2 :
Based upon the calculated value divide into various zones
Based upon the calculated value divide into various zones
§ Zone 1 (Forward) means 80% of your protected
line length.
§ Zone 2 (Forward) means 100% of protected line
length + 20% Adjacent Shortest line
§ Zone 3 (Forward) means 100% of protected line
length + 50% Adjacent Longest line.
§ Zone 4 (Reverse) means 10% of protected line.
37) Difference
between CT class 0.2 and 0.2S?
§ 0.2S & 0.5S: Special type of measurement CTs they
guarantee the declared accuracy, even with
20% loading. And some definite error can be defined even with a load as low as 1%. Thus they are suitable for industries where loads are commissioned in steps or stages. Also for tariff metering purposes.
20% loading. And some definite error can be defined even with a load as low as 1%. Thus they are suitable for industries where loads are commissioned in steps or stages. Also for tariff metering purposes.
§ 0.2S: Special class for metering. It is more accurate than 0.2
classes. Generally if we use 0.2s class CT than VA burden of core is also come
down.
§ In 0.2 classes CT, ratio & phase angle
errors must be within the specified limits at 5%, 20%, 100% & 120% of rated
secondary current. Whereas in 0.2s class CT, ratio & phase angle errors
must be within the specified limits at 1%, 5%, 20%, 100% & 120% of rated
secondary current. Also in 0.2s class, Ratio & Phase angle errors limits
are lower than 0.2 classes.
38) Why we use
inductors
§ Inductors have the property to oppose sudden
changes in Current. When connected to the primary side of transformer, if
any sudden short circuit (very high) current flows due to some fault in the system,
the inductor will oppose the flow of that current saving the transformer.
§ Secondly, for the problem of lagging current.
Capacitors are connected across the inductor to improve the lagging current. So
Mainly Inductor is used to (i) protected the transformer, (ii) solved the
problem of lagging current.
39) Why do we need a
bigger breaker when reverse feeding a transformer?
§ Typically the output winding is wound first and
is therefore closest to the core. When used as exciting winding a higher inrush
current results. In most cases the inrush current is 10 to 12 times the full
load current for 1/10 of a second. When the transformer is reverse fed the
inrush current can be up to 16 times greater. In this case a bigger breaker
with a higher AIC rating must be used to keep the transformer online.
40) How many types
of Neutral grounding system?
§ There are primarily three types of grounding
system which are:
§ (1)Solid grounding – The neutral point of the system is
grounded without any resistance. If the ground fault occurs, high ground
current passes through the fault. Its use is very common in low voltage system,
where line to neutral voltage is used for single phase loads.
Comments
Post a Comment